VI-6727
Addressable Control Module

CARACTERÍSTICAS
*Addressable Input and output module
*Easy Installation
*Output relay capacity :30VDC/1A
*Input circuit line detection with EOL resistor
*LPCB approved to EN 54-18:2005
VI-6727
The VI-6727 Control Interface is designed for linkage remote control of fire alarm system and fire protection system.Such as Fire extinguishing systems, water systems, smoke control systems, elevators, etc.
It can transmit action or stop signals to remote devices.
The input line has open circuit detection function with EOL resistor .It can provide a fault signal to FACP when a open circuit occurs.
CONFORMIDADE
LPCB approved EN 54-18
ESPECIFICAÇÃO
*Operating Voltage: 16-28V(Modulated-pulse)
*Standby Current: ≤0.5mA
*Alarm Current: ≤1.0mA
*Wiring: Two-wire(non-polarized)
*Temperature range: -10℃~50℃
*Humidity: ≤95%RH, (40±2℃)No condensation
*Remote Control Output Indication: Output LED Emitting
*Signal inputting Indication: Input LED Emitting
*IP Rating: 32
*Installation Base: VB-6618
*Weight: Module 65g, Base 58g
PRODUTO
DOCUMENTOS

Treinamento e suporte de produtos
Nossa equipe atenderá às suas necessidades para garantir que você possa operar, manter e maximizar o desempenho de nossos produtos de forma eficaz.

Expertise de Mercado
A VSAIL oferece soluções de proteção contra incêndio adaptadas para atender aos requisitos de segurança exclusivos de vários mercados e indústrias.
Detalhes do contato
R401, Fábrica nº 6, Estrada Xinxing nº 1, Zona de Desenvolvimento de Wuqing, Tianjin, China