VI-6157
Loop Card

FEATURES
*Control the detection loop signal
*Flexible installation method
*Strong EMC anti-interference capability
*The circuit adopts a non-polar wiring method
*Short-circuit and grounding self-protection
*Loop card to add loop circuit for addressable panel
*Single loop with capacity of 256 devices (Class A) or dual loop with capacity of 512 devices (Class B)
*LPCB approved to EN54-7
VI-6157
VI-6157 Loop Card: It is mainly
used to connect alarm devices such as smoke detectors and heat detectors, as well as control modules, sound and light alarm devices, etc. The loop adopts a non-polar wiring method, which makes on-site wiring convenient. The output end of the loop bus is equipped with multi-level protection devices to prevent the interference of the customer's bus loop signal and the impact on the equipment caused by short circuits. It adopts a flexible plug-in installation method with the controller, making it convenient to add loops in the later stage. It supports the free switching between two wiring methods, namely Class A and Class B. a single card can carry 256 points in the Class A wiring mode, and 512 points in the Class B wiring mode
COMPLIANCE
SPECIFICATION
*Operating Voltage: 16-28V(Modulated-pulse)
*Standby Current: ≤400mA
*Loop Voltage: 18V~24V pulse
*Loop Current: 0mA~200mA
*Temperature range: -10℃~50℃
*Humidity: ≤95%RH, (40±2℃)No condensation
PRODUCT
DOCUMENTS

Product Training and Support
Our team will assist your needs to ensure you can effectively operate, maintain, and maximize the performance of our products.

Market Expertise
VSAIL offers fire protection solutions tailored to meet the unique safety requirements of various markets and industries.
Contact Details
R401,No.6 Factory,No.1 Xinxing Road,Wuqing Development Zone,Tianjin China